Generally, it is not recommended to connect the contactor at the output end of the frequency converter. | ||||||
If the contactor must be connected, the following criteria should be followed: | ||||||
First, pull in the contactor first, and then start the frequency converter; | ||||||
Stop the machine, stop the frequency converter first, and then disconnect the contactor. | ||||||
It is absolutely not allowed to cut in or disconnect the contactor suddenly when the frequency converter is in operation, | ||||||
because this will cause huge impulse current, damage the frequency converter or motor, | ||||||
and may lead to explosion in serious cases. | ||||||