FAQ

What is the function of input side AC reactor?

What is the function of input side AC reactor?
key word: ac drive  
The reactor in the circuit generally has two functions:
(1) Suppress surge (voltage and current); (2) Suppress harmonic current.

Reactors are divided into input reactors, output reactors and DC reactors in the use of frequency converters.

Different reactors have different functions on the frequency converter.
input reactor
It is used to limit the current impact caused by the sudden change of power grid voltage and switching overvoltage, 
smooth the peak pulse contained in the power supply voltage, 
or smooth the voltage defects generated during the commutation of bridge rectifier circuit, 
effectively protect the frequency converter and improve the power factor. 
It can not only prevent the interference from the power grid, 
but also reduce the pollution of harmonic current generated by the rectifier unit to the power grid.
output choke
The main function is to compensate the influence of the distributed capacitance of the long line (20-200m),
reduce the motor ground leakage current, suppress the output harmonic current, 
improve the output high-frequency impedance, and effectively suppress dv/dt.
Reduce the high-frequency leakage current, protect the frequency converter and reduce the equipment noise.
DC reactor
t is connected between the DC rectification link and inverter link of the frequency conversion system. 
Its main purpose is to limit the AC component superimposed on the DC current to a specified value,
keep the rectifier current continuous, reduce the current pulse value, 
make the inverter link operate more stably and improve the power factor of the frequency converter.